Firmware Upgrade
8. Click Connect.
In the “Atmel – Flip” window, in the Operations Flow column, the Run
button is active, and the name of the chip appears as the name of the third
column: AT89C51RD2.
Verify that in the Buffer Information column, the “HEX File: PL8.hex”
appears.
Figure 12: Atmel – Flip Window (Connected)
9. Click Run.
After each stage of the operation is completed, the check-box for that
stage becomes colored green
1
.
When the operation is completed, all 4 check-boxes will be colored green
and the status bar message: Memory Verify Pass appears
2
1 See also the blue progress indicator on the status bar
:
2 If an error message: “Not Finished” shows, click Run again